 LAZ-04 Double Skin Tank Leak Detector - Vacuum

LAZ-04 Double Skin Tank Leak Detector - Vacuum


Class I (EN 13160-1:2003) leak detector, high vacuum based, for use with double-skinned tanks and single-skinned tanks with internal lining.
The unit is designed for monitoring above ground and underground tanks containing inflammable liquids of danger class A III as well as non-inflammable, water polluting liquids and urea solutions 32,5 % (AdBlue®). Also suitable for renovating double-skinned tanks which were previously monitored with leak detection fluid.(Refer to the operating instructions for a definition of the stored media).

Eurovac 04-1 is adjusted for an alarm vacuum level of 325mbar and approved for tanks up to 2.9m Ø  whereby the suction tube connection may end at the top of the tank. If mounted outdoors, special installation requirements have to be observed, e.g. protective housing, greater internal capillary tube diameters (6 mm), condensate traps.For tanks according to EN 12285-1, EN 12285-2 design A, DIN 6618-2, 6619-1, 6623-1, 6624-1 as well as equivalent tanks made from steel or equivalent approved tanks made from plastic, provided that they have double walls or are equipped with an approved leak protection lining (internal lining) according to EN 12285-1 or by analogous application of EN 12285-1.For tanks according to DIN 6625-1 which are equipped with an approved leak protection lining (internal lining) and cylindrical, rectangular or spherical tanks made from reinforced concrete or equivalent, approved tanks made from other materials which are equipped with an approved leak protection lining (internal lining).

Not for use on tanks containing inflammable liquids (Use LAD series).


 LAG 14 Double Skin Tank Leak Detector - Liquid Filled

LAG 14 Double Skin Tank Leak Detector - Liquid Filled


This class II (EN 13160-1: 2003) leak detector with an intrinsically safe probe circuit is designed for double-skinned tanks containing liquid in the interstitial space.
The unit is designed for monitoring inflammable liquids of danger classes A I, A II, A III and B stored above ground and non-inflammable water-polluting liquids.
The system consists of a control unit, a container for leak monitoring fluid and a probe. CE-certified control unit with visual and audible alarms, test button and increased interference protection. With relay for connection of additional alarm equipment.

Approved for tanks according to EN 12285-1, EN 12285-2, DIN 6618-1, DIN 6619-1, DIN 6623-1, DIN 6624-1.The container for leak monitoring fluid is made from antistatic plastic and can be mounted in hazardous areas of zones I and II (e.g. access chamber of petrol tanks). The control unit can be panel mounted


 

 

OSA Oil Separator Alarm 

OSA Oil Separator Alarm


The OSA Oil Separator Alarm monitors the level of the separated liquid in oil/petrol separators and generates an alarm signal when it is necessary to empty the separator.

It consists of an alarm unit and an ES4 capacitance sensor for detecting the layer level. The unit has two relay outputs, audio/visual alarms, test and reset buttons and also monitors the sensor for shorts or cable breaks in the sensor circuit.The ES4 capacitance probe is mounted at least 150mm below the normal level of the separator.When the oil or petrol layer reaches the critical level, the unit generates an alarm signal. 

 

 

 

 

LAD-R  Double Skin Pipe Leak Detector - Pressurised 

LAD-R Double Skin Pipe Leak Detector - Pressurised

 The LAD-R pressure type leak detector contains the following elements in an impact-resistant housing display elements and controls, a printed circuit board with the electronic components for processing the output signal and connections for the remote pressure gauge with two switching contacts or individual high and low pressure switches as required.


The LAD-R monitors the over/under pressure in the interstitial space of a pipe or storage tank and generates an alarm signal in the case of a pressure drop or increase.The alarm is indicated audibly and visibly and is also available via a voltage-free relay contact (1 changeover contact). The switch points for low and high pressure can be adjusted via the two switching contacts of the remote pressure gauge by means of an adjustment spanner. The total monitored interstitial space volume must not exceed 1200 litres per LAD-R.Constructed of aluminium, the manifolds are available with 1 to 6 connections and fitted with a 1, 5 or 10 bar pressure gauge according to requirements . Connections are designed for 6mm plastic or copper pipes.

Supplied with one way manifold as standard.

 

 

SOL 3000 Solar Powered Oil Separator Alarm


The SOL 3000 has been designed to monitor hydrocarbon levels in oil separators and interceptors in locations where mains power is unavailable.

The system comprises of an IP65 rated enclosure containing an ATEX approved oil separator alarm, solar panel, battery and monitoring electronics mounted on an angled galvanised steel pole and flange assembly with an integral 10m sensor cable which may be extended to a maximum of 300m. An optional wall mounting bracket is also available.A specially designed fail-safe solid state sensor is mounted at the required level in the separator chamber.
A high intensity flashing beacon on the top of the enclosure warns that the separator requires emptying, or of sensor fault (short/open circuit) conditions.An integral solar panel trickle-charges the heavy duty lead acid 18AH battery. A Test/Reset button is provided to check operation by simulating an alarm condition.
To conserve battery power, the SOL 3000 is active for 20 seconds every 60 minutes or as required (factory option).If an alarm condition is present, the high intensity beacon will flash until the alarm condition is cleared.There is sufficient battery capacity for the beacon to operate for 7 days in poor light conditions.